CVE-2021-31882
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC)...
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
Attack profile
How easy it is to exploit
- Attack vector
- Adjacent network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
What an attacker can affect
- Confidentiality
- None
- Integrity
- None
- Availability
- High
Exploit likelihood
What each source reports
CVE List Score used
6.5
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
- Record
CVE-2021-31882- CVSS 3.1
- 6.5 Medium
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H - Weakness
- CWE-119
- Updated
- 2026-11-02
EUVDEUVD-2021-18757
6.5
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
- Record
EUVD-2021-18757- CVSS 3.1
- 6.5 Medium
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H - Updated
- 2026-11-02
GitHub AdvisoriesGHSA-w2w7-g4vg-h87m
7.5
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC)...
A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions), APOGEE PXC Compact (P2 Ethernet) (All versions), APOGEE PXC Modular (BACnet) (All versions), APOGEE PXC Modular (P2 Ethernet) (All versions), Capital VSTAR (All versions), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.4), Nucleus Source Code (All versions), TALON TC Compact (BACnet) (All versions), TALON TC Modular (BACnet) (All versions). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
- Record
GHSA-w2w7-g4vg-h87m- CVSS 3.1
- 7.5 High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H - Weakness
- CWE-119
- Updated
- 2026-11-02
NVD
6.5
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303). The DHCP client application does not validate the length of the Domain Name Server IP option(s) (0x06) when processing DHCP ACK packets. This may lead to Denial-of-Service conditions. (FSMD-2021-0011)
- Record
CVE-2021-31882- CVSS 3.1
- 6.5 Medium
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H - CVSS 3.1
- 7.5 High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H - CVSS 2.0
- 5.0 Medium
AV:N/AC:L/Au:N/C:N/I:N/A:P - Weakness
- CWE-119
- Updated
- 2026-11-02
Affected products
- siemens capital embedded ar classic 431-422
- siemens capital embedded ar classic r20-11
- siemens apogee modular building controller firmware
- siemens apogee modular equiment controller firmware
- siemens apogee pxc compact firmware
- siemens apogee pxc modular firmware
- siemens capital vstar
- siemens nucleus net
- siemens nucleus readystart v3
- siemens nucleus source code
- siemens talon tc compact firmware
- siemens talon tc modular firmware
History
| Recorded | Changed | Sources |
|---|---|---|
| first indexed | CVE List, EUVD, GitHub Advisories, NVD |
Dates are when Every CVE recorded each change. Upstream dates may differ.
In short
CVE-2021-31882 is a medium vulnerability (CVSS 6.5) in Siemens Capital Embedded Ar Classic 431-422, published November 9, 2021. No source lists public exploit code. EPSS puts the chance of exploitation in the next 30 days at 1.52%, the 74th percentile. No source names a fixed version.
References
cert-portal.siemens.com/productcert/pdf/ssa-114589.pdf
cert-portal.siemens.com/productcert/pdf/ssa-044112.pdf
cert-portal.siemens.com/productcert/pdf/ssa-620288.pdf
cert-portal.siemens.com/productcert/html/ssa-114589.html
cert-portal.siemens.com/productcert/html/ssa-044112.html
cert-portal.siemens.com/productcert/html/ssa-620288.html
nvd.nist.gov/vuln/detail/CVE-2021-31882
github.com/advisories/GHSA-w2w7-g4vg-h87m