CVE-2022-33174
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows...
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Attack profile
How easy it is to exploit
- Attack vector
- Network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
What an attacker can affect
- Confidentiality
- High
- Integrity
- High
- Availability
- High
Exploit likelihood
What each source reports
CVE List Score used
9.8
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
- Record
CVE-2022-33174- CVSS 3.1
- 9.8 Critical
CVSS:3.1/AC:L/AV:N/A:H/C:H/I:H/PR:N/S:U/UI:N - Updated
- 2026-11-02
EUVDEUVD-2022-36218
9.8
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
- Record
EUVD-2022-36218- CVSS 3.1
- 9.8 Critical
CVSS:3.1/AC:L/AV:N/A:H/C:H/I:H/PR:N/S:U/UI:N - Updated
- 2026-11-03
GitHub AdvisoriesGHSA-583h-x99p-fmcc
7.5
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows...
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
- Record
GHSA-583h-x99p-fmcc- CVSS 3.1
- 7.5 High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N - Weakness
- CWE-863
- Updated
- 2026-11-02
NVD
9.8
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
- Record
CVE-2022-33174- CVSS 3.1
- 9.8 Critical
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H - CVSS 3.1
- 7.5 High
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N - CVSS 2.0
- 5.0 Medium
AV:N/AC:L/Au:N/C:P/I:N/A:N - Weakness
- CWE-863
- Updated
- 2026-11-02
Affected products
Public exploits
Links only. Every CVE stores no exploit code.
| Source | Link | Date |
|---|---|---|
| Nuclei | Powertek Firmware <3.30.30 - Authorization Bypass | |
| PoC in GitHub | Henry4E36/CVE-2022-33174 | 2022-09-02 |
History
| Recorded | Changed | Sources |
|---|---|---|
| aliases | EUVD | |
| first indexed | CVE List, GitHub Advisories, Nuclei, NVD, PoC in GitHub |
Dates are when Every CVE recorded each change. Upstream dates may differ.
In short
CVE-2022-33174 is a critical vulnerability (CVSS 9.8) in Powertekpdus Basic Pdu Firmware, published June 13, 2022. Public exploit code exists. EPSS puts the chance of exploitation in the next 30 days at 14.1%, the 96th percentile. No source names a fixed version.