CVE-2026-15203
Debug interfaces are accessible by default in Danfoss iC7 Automation SP, iC7 Marine and iC7 7Hybrid software
Improper access control in debug and engineering interfaces in Danfoss iC7-Automation SP, iC7-Marine, and iC7-Hybrid GR3 allows attackers to gain read/write access to internal values, upload and execute unsigned applications, and upload unsigned EEPROM data and firmware via exposed service interfaces and software update mechanisms
Attack profile
How easy it is to exploit
- Attack vector
- Network
- Complexity
- Low
- Privileges needed
- None
- User interaction
- None
What an attacker can affect
- Confidentiality
- High
- Integrity
- High
- Availability
- High
Exploit likelihood
What each source reports
CVE List Score used
9.3
Debug interfaces are accessible by default in Danfoss iC7 Automation SP, iC7 Marine and iC7 7Hybrid software
Improper access control in debug and engineering interfaces in Danfoss iC7-Automation SP, iC7-Marine, and iC7-Hybrid GR3 allows attackers to gain read/write access to internal values, upload and execute unsigned applications, and upload unsigned EEPROM data and firmware via exposed service interfaces and software update mechanisms
- Record
CVE-2026-15203- CVSS 4.0
- 9.3 Critical
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:L - Weakness
- CWE-1191
- Updated
- 2026-11-02
EUVDEUVD-2026-66251
9.3
Improper access control in debug and engineering interfaces in Danfoss iC7-Automation SP, iC7-Marine, and iC7-Hybrid GR3 allows attackers to gain read/write access to internal values, upload and execute unsigned applications, and upload unsigned EEPROM data and firmware via exposed service interfaces and software update mechanisms
- Record
EUVD-2026-66251- CVSS 4.0
- 9.3 Critical
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:L - Updated
- 2026-11-02
GitHub AdvisoriesGHSA-m45v-v2rr-g2hr
9.3
Improper access control in debug and engineering interfaces in Danfoss iC7-Automation SP, iC7...
Improper access control in debug and engineering interfaces in Danfoss iC7-Automation SP, iC7-Marine, and iC7-Hybrid GR3 allows attackers to gain read/write access to internal values, upload and execute unsigned applications, and upload unsigned EEPROM data and firmware via exposed service interfaces and software update mechanisms
- Record
GHSA-m45v-v2rr-g2hr- CVSS 4.0
- 9.3 Critical
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:L/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X - Weakness
- CWE-1191
- Updated
- 2026-11-02
NVD
9.3
Improper access control in debug and engineering interfaces in Danfoss iC7-Automation SP, iC7-Marine, and iC7-Hybrid GR3 allows attackers to gain read/write access to internal values, upload and execute unsigned applications, and upload unsigned EEPROM data and firmware via exposed service interfaces and software update mechanisms
- Record
CVE-2026-15203- CVSS 4.0
- 9.3 Critical
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:L/SI:L/SA:L/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X - Weakness
- CWE-1191
- Updated
- 2026-11-02
Affected products
History
| Recorded | Changed | Sources |
|---|---|---|
| first indexed | CVE List, EUVD, GitHub Advisories, NVD |
Dates are when Every CVE recorded each change. Upstream dates may differ.
In short
CVE-2026-15203 is a critical vulnerability (CVSS 9.3) in Danfoss Ic7-automation Sp, published August 26, 2026. No source lists public exploit code. EPSS puts the chance of exploitation in the next 30 days at 0.48%, the 41st percentile. No source names a fixed version.